GU FIBERGLASS REINFORCED PLASTIC MANHOLE BASE LINER

(A) Scope
The manhole base liner shall be a FIBERGLASS REINFORCED PLASTIC (F.R.P.) BASE LINER SYSTEM, which is resistant to the chemical environment normally found in wastewater transmission systems. The F.R.P. Base Liner shall be a non-load bearing component integrally cast and adequately anchored inside new precast concrete manhole base sections during concrete casting process at the concrete precaster's manufacturing facility
(B) FIBERGLASS MANHOLE BASE LINER
(1) The prefabricated F.R.P. base liner shall be a one piece construction of unlayered, homogenous composite with minimum thickness shall be 1/8" (3 mm) and shall be in lengths and nominal inside diameters corresponding to the precast concrete base section.
(2) The prefabricated F.R.P. manhole base liner shall include full flow channels with side walls to the crown of the pipe; inner surface of the bench to have an anti-skid pattern; watertight gasketed pipe bell connections or F.R.P. / PVC boot hole sleeves to suit specific pipe types, grade and alignment, shall be monolithically attached to prefabricated F.R.P. base liners to extend to the outside profile of the precast concrete structure per drawing details.
(3) The outer surface of the liner to be aggregate coated and have steel spirals/ lattice bonded to the F.R.P. to insure adequate anchoring to concrete base sections to pass vacuum test with 10" of negative pressure.
(C) INSTALLATION IN PRECAST CONCRETE
(1) The F.R.P. base liner shall be cast integral with the precast concrete manhole base section in accordance with the liner manufacturer's specifications. The liner must be fully supported during the casting process; lifting devices shall not penetrate inside walls F.R.P. base liner.
(2) Inside F.R.P. liner surfaces shall be free of bulges, dents and other defects that result in a variation of inside diameter of more than 1/4" (7 mm) for base liner flow channel and pipe connections. The precast concrete pipe penetration joint surfaces shall be free of excess concrete at external and internal surfaces to insure proper seal of pipe connection and F.R.P. liner.
(D) FIELD ASSEMBLY AND INSPECTION PRECAST CONCRETE MANHOLE WITH F.R.P. LINER
(1) During the field installation of F.R.P. lined precast manhole base sections; all pipe connections are to be sealed per the liner manufacturer's standard method and details. Precast concrete sections shall be sealed as prescribed by precast manufacturer and utility specifications.
(2) The interior surfaces of the liner shall be completely free from pinholes, cracks, pits or defects that are detrimental to the intended use of the F.R.P. base liner. No F.R.P. base liner shall have holes, or openings, which will permit the passage of liquid or gases through the liner wall to precast concrete. There shall be no exposed concrete mortar through inside liner surface to include (but not limited to) pipe penetrations. All mechanical anchor attachments through liner surfaces must be sealed with an approved elastomeric sealant. Consult liner manufacturer for specific information regarding approved sealant supplier list and availability.


 


<